Siemens · SINAMICS G120
A static '1' signal is present at the F-DI input designated for safe acknowledgment of safety functions. This indicates an incorrect input state, preventing proper acknowledgment or causing a fault, which can stop operations or prevent safety functions from being reset.
Click steps to track your progress.
Identify the specific F-DI input configured for safe acknowledgment (refer to relevant P-parameters, e.g., P60001, P60002).
Measure the voltage at the identified F-DI input terminal (e.g., X124/1) with a multimeter to confirm a static 24VDC signal.
Temporarily disconnect the external device connected to the acknowledgment F-DI input to determine if the signal goes low (0VDC).
Inspect the wiring for the acknowledgment F-DI input for any short circuits to 24VDC or damaged insulation.
Verify the parameterization of the F-DI input (e.g., P60001, P60002) to ensure it is correctly assigned as a safe acknowledgment input and not misused.