F01680

Expected fault during component replacement

Siemens · SINAMICS G120

What does F01680 mean?

This fault is part of a group (F01641, F01650, F01680, F30680) that is expected to occur temporarily during specific corrective maintenance procedures, such as replacing a Control Unit or the entire inverter. It does not indicate a persistent problem if the full replacement and recommissioning steps are followed. The risk is negligible if acknowledged as part of the procedure.

Common Causes

  • A Control Unit (CU) or Power Module (PM) has been replaced, and the system is detecting hardware differences during initial power-up.
  • Firmware version mismatch between a newly installed component and existing system components, causing an initialization error.
  • Parameter inconsistencies or missing data after a component replacement, especially if parameters were not backed up and restored.
  • Incorrect installation or seating of a newly replaced module (e.g., loose connections on the Control Unit).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Confirm that the component replacement (e.g., Control Unit, Power Module) was completed successfully and all connections are secure.

  2. 2

    2. Perform a parameter reset to factory defaults (e.g., p0010 = 30, p0970 = 1) if parameter backup/restore was not performed prior to replacement.

  3. 3

    3. Download the correct parameter set from a backup (if available) to the newly installed component using commissioning software (e.g., STARTER, TIA Portal).

  4. 4

    4. Execute a firmware update on the replaced component to match the system's current firmware version, if necessary.

  5. 5

    5. Cycle power to the drive system after ensuring all modules are correctly installed and parameters are loaded.