Siemens · SINAMICS G120
The Safely Limited Speed (SLS) function is not enabled, even though it's required or configured for the application. This prevents the system from limiting speed safely, potentially leading to hazardous overspeed conditions if the drive operates outside its safe limits.
Click steps to track your progress.
1. Check parameter p9500 (SLS enable) and ensure it is set to 1 if Safely Limited Speed is required for the application.
2. Verify the status of the external safety PLC or safety relay outputs that provide the enable signal for SLS, checking for voltage levels on relevant safety terminals.
3. Inspect the wiring and connections of the safety input terminals (e.g., safety input 1, safety input 2) for SLS for damage or improper termination.
4. Confirm that any preceding safety functions (e.g., STO) are correctly enabled and not causing a lockout for SLS.
5. Perform a safety reset (e.g., by cycling the STO inputs or using a dedicated safety reset parameter like p9699) after addressing the root cause.