Siemens · SINAMICS G120
A parameter value is not permitted or is incorrect for encoderless operation, indicating an invalid configuration for the current operating mode. This can lead to improper motor control and potentially unsafe conditions if speed or position feedback is compromised.
Click steps to track your progress.
1. Verify parameter p1300 (Control mode selection) is correctly set for encoderless operation (e.g., 20 or 21 for V/f control or vector control without sensor).
2. Check parameters related to encoder configuration (e.g., p0400, p0404, p0408) and ensure they are either set to 0 or correspond to 'no encoder' settings.
3. Confirm that no physical encoder is connected to the Control Unit's encoder terminals (e.g., X130) if encoderless operation is desired.
4. Perform a motor identification run (e.g., p1900 = 1 or 2) after ensuring all encoder-related parameters are correctly set for encoderless mode.
5. Review the complete parameter set for any remnants of previous encoder configurations that might conflict with the current setup.