Siemens · SINAMICS G120
The Safe Torque Off (STO) function is active, meaning the motor's torque-generating energy is prevented, and the motor is freely rotating or at a standstill. This is a safety state initiated to prevent unintended startup, not necessarily a fault.
Click steps to track your progress.
Verify the status of the STO safety input signals by measuring voltage at the dedicated terminals (e.g., X1:DI0, X1:DI1) or checking Profisafe status word (r0945.x).
Examine the external safety chain (e.g., E-stop buttons, safety gate switches, safety relays) to ensure all contacts are closed (e.g., continuity test across relay contacts).
Confirm that no upstream safety function (e.g., SS1) is intentionally activating STO by monitoring diagnostic bits r0947.x.
Measure voltage across the STO terminals to ensure the required 24VDC is present for deactivation (e.g., 24VDC between X1:DI0 and X1:DI_RET).
Reset the safety input or the upstream safety controller (e.g., F-PLC) to remove the STO activation command.