F30680

Expected fault during component replacement

Siemens · SINAMICS G120

What does F30680 mean?

This fault is part of a group (F01641, F01650, F01680, F30680) that is expected to occur temporarily during specific corrective maintenance procedures, such as replacing a Control Unit or the entire inverter. It does not indicate a persistent problem if the full replacement and recommissioning steps are followed. The risk is negligible if acknowledged as part of the procedure.

Common Causes

  • Power unit detected no valid Control Unit firmware or missing licensing information during initial boot sequence.
  • Hardware incompatibility between the newly replaced Control Unit and the existing power module (e.g., incorrect hardware revision for integration).
  • Loss of internal communication between critical sub-modules (e.g., temperature or current sensors) due to incorrect mounting or misaligned connectors.
  • Control unit is inserted but not correctly powered or initialized, preventing it from establishing necessary communication with other modules.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Confirm that the Control Unit's locking mechanism is fully engaged and that it is seated flush with the power module chassis.

  2. 2

    2. Verify the part numbers of the replaced Control Unit and the existing power module against manufacturer compatibility lists and documentation.

  3. 3

    3. Perform a full power cycle of the entire drive system, waiting at least 30 seconds after power-off before reapplying power.

  4. 4

    4. Check for any visible damage on the backplane connectors of both the Control Unit and the slot it plugs into, ensuring pins are straight and clean.

  5. 5

    5. Attempt a system restore or firmware re-flash procedure for the Control Unit if proper seating and compatibility are confirmed, using vendor-specific commissioning tools.

Browse all codes in this manual (109)
Verified technical data. Last updated: April 2026