Siemens · SINAMICS G120
An error occurred during the forced checking procedure (test stop) for the fail-safe digital output, indicating a potential wiring issue or malfunction of the output itself. This means the safety test failed, and the fail-safe output cannot be trusted.
Click steps to track your progress.
Identify the specific fail-safe digital output channel (e.g., F-DO0) that failed the test, as indicated by r2124.
Measure the voltage and current at the F-DO terminals (e.g., X1:F-DO0 and X1:F-DO_RET) during a manual test pulse activation if available.
Perform a continuity check on the wiring from the inverter F-DO terminal to the external load (e.g., safety contactor coil, resistor R1).
Temporarily disconnect the external load from the F-DO and repeat the test to determine if the load (e.g., contactor K1) itself is faulty.
Verify the F-DO parameterization (P30702, P30703) including output type (e.g., 2-channel with test pulses) and pulse duration settings.
Observe diagnostic LEDs on the F-DO module for specific indications of the test error (e.g., Red LED on F-DO channel).