Vacon · 100 FLOW Application Guide
A malfunction in the supply voltage or issues with input fuses/cables are detected. The supervision for this fault requires a minimum load of 10-20% to function correctly. This fault indicates a problem with the incoming power supply to the drive, which can cause motor and drive instability.
Click steps to track your progress.
Measure all three phase-to-phase input voltages (L1-L2, L2-L3, L3-L1) at the drive's input terminals.
Check continuity of all input fuses (e.g., F1, F2, F3) using an ohmmeter, replacing any open fuses.
Inspect all input power wiring for loose connections, damage, or signs of overheating from the main breaker to the drive.
Verify the supply voltage monitoring parameters (e.g., P4-10 Input Phase Loss Threshold) are appropriately configured for the application.
Measure the current balance between input phases (L1, L2, L3) with a clamp meter during operation, looking for significant imbalances.