EL
ErrorLib
Brands
||
  1. Home
  2. Vacon
  3. 100 FLOW Application Guide
  4. 105
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

105

External PID Feedback Supervision Fault

Vacon · 100 FLOW Application Guide

What does 105 mean?

The feedback value for the external PID controller is outside its configured supervision limits (P3.14.4.2 and P3.14.4.3) for a specified delay (P3.14.4.4). This indicates a problem with the external process feedback, potentially leading to unstable control or incorrect process regulation. It signifies a deviation in the external process variable.

Common Causes

  • External process sensor providing feedback to the external PID controller is malfunctioning or has failed, sending an invalid signal.
  • Feedback signal cable from the external sensor to the drive's designated analog input is damaged, disconnected, or suffering from interference.
  • External PID supervision limits (P3.14.4.2 for low limit, P3.14.4.3 for high limit) are set too tightly for the external process's normal operating range.
  • The external process is experiencing a severe disturbance, causing the feedback value to deviate beyond the configured supervision limits.
  • The delay time for supervision (P3.14.4.4) is set too short, triggering the fault prematurely during normal process transients.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the physical external process feedback signal at the drive's assigned analog input terminal using a multimeter, comparing it to the actual process variable reading.

  2. 2

    2. Inspect the wiring from the external process sensor to the drive's analog input for continuity, proper shielding, and secure connections.

  3. 3

    3. Check the external sensor and its associated controller for proper operation, including its power supply, output range, and calibration.

  4. 4

    4. Review and adjust the external PID feedback supervision parameters: P3.14.4.2 (low limit), P3.14.4.3 (high limit), and P3.14.4.4 (delay time) to match the process's expected behavior.

  5. 5

    5. Observe the external process for any abnormal conditions (e.g., external valve failure, pump issues) that could cause the feedback deviation.

  6. 6

    6. Ensure the analog input scaling (e.g., P3.3.2.2 for AI2 min value, P3.3.2.3 for AI2 max value) for the feedback signal is correctly configured.

Browse all codes in this manual (73)
Verified technical data. Last updated: April 2026

Related Faults

1Overcurrent10Input Phase Fault101PID Feedback Supervision Fault (PID1)
Source: Vacon 100 FLOW Application Guide
View Official PDFSearch more codes in this manual