Vacon · 100 FLOW Application Guide
This fault indicates that the drive's current measurement system has detected zero current in one of the motor phases. This typically points to a disconnection or malfunction in the motor or its cabling, or an issue with an associated du/dt or sinus filter. Continued operation with a missing phase can lead to motor damage or reduced performance.
Click steps to track your progress.
1. With power off and safety measures applied, measure resistance between drive output terminals (U-V, V-W, W-U) and compare to expected motor winding resistance.
2. Disconnect motor power cables at the drive output terminals (T1, T2, T3) and perform a continuity test on each cable phase from the drive to the motor.
3. Perform a winding resistance test on the motor itself by measuring resistance between U, V, and W terminals at the motor side, expecting balanced readings.
4. Verify all terminal connections at the drive output (U, V, W) and the motor input for tightness and proper seating.
5. If an output choke or filter is installed, inspect its connections and internal continuity across each phase.