The drive is unable to convert one or more values for Fieldbus Process Data Out because the data type is not correctly specified or incompatible. This prevents the drive from accurately transmitting process data over the fieldbus. Incorrect data types can lead to misinterpretation by the fieldbus master and potential control anomalies.
Click steps to track your progress.
1. Review the Fieldbus Process Data Out mapping (e.g., P4-01 to P4-XX) and ensure the selected drive parameters are compatible with the configured fieldbus data types.
2. Verify the scaling factor parameters (e.g., P4-YY for specific output scaling) for the Process Data Out entry to ensure it results in a representable value.
3. Check the drive's documentation for the selected parameter to confirm its native data type (e.g., integer, float, word) and range.
4. Adjust the fieldbus master (PLC) configuration to expect the correct data type for the specific Process Data Out from the drive.