Vacon · 100 FLOW Application Guide
This fault, specific to customer-specific applications, indicates a malfunction during the start angle identification process. Possible causes include rotor movement during identification or a mismatch between the new and old angle values. This prevents accurate motor control and startup.
Click steps to track your progress.
Ensure the motor is completely decoupled from the mechanical load or that the load is absolutely stationary before initiating any auto-tune function (e.g., P9-01 set to 1).
Verify all motor nameplate parameters (P3-01 to P3-08) are accurately entered into the drive, paying close attention to motor rated current and voltage.
Confirm motor cable connections (U, V, W) are tight and free of corrosion at both the motor and drive terminals.
If the motor is exceptionally small or large compared to the drive's rating, consider if it's within the drive's operating envelope for accurate identification.
Attempt to run the motor in V/Hz control mode (e.g., P1-01 set to 0) to verify basic motor operation before re-attempting advanced control.