Vacon · 100 FLOW Application Guide
The drive cannot perform a startup because a new software (firmware or application), parameter setting, or other file affecting operation was loaded while a Run request was ON. The drive prevents startup to ensure configuration integrity and prevent improper operation.
Click steps to track your progress.
Cycle the main input power to the drive (power off, wait for DC link discharge, power on).
Ensure that any run command signals (e.g., digital input terminal 1 (DI1), communication command) are deactivated before attempting further configuration changes.
Verify that no external control system is sending a persistent run command. Temporarily disconnect control wiring from terminals like DI1 to rule this out.
Re-check the drive's run/stop source parameter (e.g., P0-10) to ensure it is correctly configured for the desired control method (e.g., HMI, DI, fieldbus).
If a parameter file was recently uploaded, ensure the correct file version for the current application is active after cycling power.