Vacon · 100 FLOW Application Guide
The drive's Fire mode is currently enabled, which intentionally disables certain drive protections to ensure continuous operation in emergency situations. This is an informational alarm indicating a specific operational state, and it resets automatically when Fire mode is disabled.
Click steps to track your progress.
Verify the state of the digital input (e.g., DI3) configured for Fire Mode activation using a multimeter, ensuring it is not inadvertently active (e.g., 24VDC present).
Check the drive's operation mode parameter (e.g., P9-20 Fire Mode Status) to confirm if it has been manually set.
Examine the logic of the external control system (PLC, BMS) that interfaces with the drive's fire mode input/command.
Review the drive's parameter settings (e.g., P9-21 Fire Mode Action) to understand which protections are disabled in this mode.
To exit Fire Mode, deactivate the corresponding digital input (e.g., remove 24VDC from DI3) or change the HMI parameter (P9-20) back to "Disabled".