383

Option Board Removed (Slot C)

Vacon · 100 FLOW Application Guide

What does 383 mean?

An option board configured for slot C has been physically removed from the drive. This indicates that the functionalities provided by this option board are now unavailable. The drive will register this as an error until the issue is addressed.

Common Causes

  • The option board configured for Slot C (as indicated by parameter P5-03) has been physically removed or dislodged.
  • Accidental removal of the option board during nearby equipment adjustments or drive troubleshooting.
  • Installation of an incompatible option board type in Slot C, which the drive fails to recognize after configuration.
  • Internal connector damage within Slot C on the drive's control board, preventing proper board detection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power down the drive and physically re-install the option board into Slot C, ensuring full engagement of the connector.

  2. 2

    2. Check parameter P5-03 to confirm it is set correctly for the type of option board expected in Slot C.

  3. 3

    3. Examine the option board for physical damage or missing components, verifying its identification label.

  4. 4

    4. If available, swap the option board with a known working board of the same type to isolate the fault to the board itself.

  5. 5

    5. Cycle the drive's power after re-seating the board and observe the drive's status on the HMI.