Vacon · 100 FLOW Application Guide
One or more analog input signals are below 50% of their minimum signal range. This suggests a defective or loose control cable, or a malfunction in the signal source itself. This can lead to incorrect control inputs and affect drive operation.
Click steps to track your progress.
1. Check the physical wiring connections at the drive's analog input terminals (e.g., AI1, AI2) for looseness, corrosion, or damage.
2. Using a multimeter, measure the voltage or current directly at the sensor's output terminals to confirm the actual signal value.
3. Verify the analog input parameters (e.g., P3.3.1.1 for AI1 type, P3.3.1.2 for AI1 min value, P3.3.1.4 for AI1 supervision fault threshold) match the connected sensor's specifications.
4. Trace the analog input cable for damage or breaks, checking continuity from the sensor to the drive's input terminals.
5. Temporarily connect a known good signal source (e.g., potentiometer, signal generator) to the drive's analog input to test the drive's input circuit functionality.