Vacon · 100 FLOW Application Guide
The connection between the control panel (keypad) and the drive is defective, preventing proper communication. This could be due to a faulty cable, improper seating of the keypad, or a damaged control panel itself. Loss of communication means the drive cannot be controlled or monitored via the keypad.
Click steps to track your progress.
1. Power down the drive, then disconnect and firmly re-seat the keypad cable at both the drive's communication port and the keypad module.
2. Inspect the keypad cable for any visible damage (e.g., cuts, pinched sections, bent pins at connectors) and replace it if defects are found.
3. If using a remote keypad, ensure the cable length does not exceed the manufacturer's specified maximum for reliable data transmission.
4. Temporarily connect a different, known good keypad to the drive's communication port to isolate whether the original keypad is faulty.
5. Check for strong EMI sources near the keypad communication cable and reroute the cable if necessary, ensuring proper shielding and grounding practices.