Vacon · 100 FLOW Application Guide
The drive's start command has been blocked, primarily to prevent accidental motor rotation, especially during the initial power-up sequence. This is a safety feature to ensure the system is in a known, safe state before operation. The drive will not operate until this prevention is cleared.
Click steps to track your progress.
1. Verify the status of all safety inputs (e.g., STO terminals, emergency stop circuits) and ensure they are disengaged.
2. Check the drive's status word (P0-01) for any active faults and perform a fault reset if required.
3. Confirm the speed reference input (e.g., analog input terminal AI1 or fieldbus reference) is providing a non-zero value.
4. Review parameter P1-11 (Auto Restart) and adjust it if a different automatic start behavior is desired.
5. Measure the voltage across the digital input terminals configured for the run command (e.g., DI1 to GND) to confirm signal presence.