11

Output phase supervision

Vacon · NX All-in-One Application

What does 11 mean?

The drive's current measurement system detects no current flowing in one of the motor phases. This typically signifies an open circuit in the motor's power path, potentially due to a disconnected motor cable, a break in the motor winding, or a faulty connection at the motor or drive terminals. This can lead to the motor operating unevenly or failing to run.

Common Causes

  • One or more phases in the motor output connection are open or shorted.
  • Motor winding fault (e.g., short circuit between phases or to ground).
  • Loose or damaged output cable connections.
  • Internal output stage failure in the frequency converter.
  • Overcurrent condition on one or more output phases.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Perform a continuity check on all motor cables (U, V, W) from the drive's output terminals to the motor's terminal box.

  2. 2

    Measure the resistance between motor phases (U-V, V-W, U-W) directly at the motor terminals — expect balanced resistance values matching the motor's specifications.

  3. 3

    Measure the insulation resistance between each motor phase (U, V, W) and motor ground using a megger at 500VDC — expect a reading greater than 1 MΩ.

Browse all codes in this manual (42)
Verified technical data. Last updated: April 2026