Vacon · NX All-in-One Application
A hardware trip (S1) has detected the DC-link voltage exceeding its safe limits. This can be caused by a deceleration time that is too short, high voltage spikes on the input power supply, or a rapid Start/Stop sequence. Subcode S2 indicates issues with overvoltage control supervision.
Click steps to track your progress.
Increase the deceleration time parameter in the drive settings to allow for slower motor braking.
If regenerative energy is an issue, consider installing an optional brake chopper and brake resistor system.
Activate or verify the settings of the drive's internal overvoltage controller.
Measure the input voltage at the drive's main power terminals to ensure it is within specified limits and stable.