Vacon · NX Liquid-Cooled Drive
The AC drive has detected an excessively high current, exceeding 4 times the nominal current (4*IH), in the motor cables. This condition typically results from a sudden heavy increase in mechanical load, a short circuit within the motor cables, or the use of an unsuitable motor for the application. Subcode S1 indicates a hardware trip, while S3 points to current controller supervision.
Click steps to track your progress.
Check the mechanical loading on the motor shaft to ensure it is within expected limits.
Inspect the motor for any signs of damage or malfunction, and verify its suitability for the connected load.
Verify the integrity of the motor cables for any signs of insulation failure or short circuits between phases or to ground.