Vacon · NX Liquid-Cooled Drive
An external electronic monitoring relay has detected an undervoltage, incorrect phase sequence, or a phase failure in the input line. The minimum threshold values are 360Vac for 400-500Vac supply and 470Vac for 525-690Vac supply, with a 0.1-second response delay. Possible causes include a missing supply phase, a blown supply fuse, incorrect mains cabling, or a grid interruption. Subcodes S1 (phase supervision diode supply) and S2 (phase supervision active front end) are available.
Click steps to track your progress.
Check the settings of the External Monitoring Device (EMD) relay for correct undervoltage thresholds, phase sequence, and response delay.
Verify the signal wiring from the EMD relay to the control unit.
Measure the incoming supply voltage at the drive input terminals across all three phases.
Check all input fuses for continuity and proper rating.
Inspect the mains cabling for correct phase connections and signs of damage.
Check the rectifying bridge for proper operation.