Vacon · NXS NXP
The hardware-level overtemperature protection for the IGBT inverter bridge has activated, indicating an excessively high short-term overload current. This can be caused by heavy motor loading or an incorrectly sized motor. Persistent high temperatures can permanently damage the IGBTs, leading to catastrophic drive failure.
Click steps to track your progress.
Check the drive's cooling fan operation and ensure heatsink fins are free from dust and debris. Verify ambient temperature is within drive specifications.
Measure motor current (P0-01) and compare against the motor nameplate and drive's rated current to confirm sustained overload conditions.
Disconnect motor cables (U, V, W) and perform a motor insulation resistance test (Megger test) and phase-to-phase resistance test to check for motor faults.
Inspect drive output terminals (U, V, W) and motor cable for signs of short circuits or insulation breakdown.
Allow the drive to cool down completely (e.g., 30 minutes) and then attempt a restart to confirm if the fault is purely thermal.