The IGBT Inverter Bridge overtemperature protection has activated, detecting excessively high short-term overload current. This can be caused by heavy motor loading or an incorrectly sized motor. Persistent high temperatures can permanently damage the IGBTs, leading to catastrophic drive failure.
Click steps to track your progress.
Record the drive's output current and motor load percentage displayed on the control panel.
Reduce the mechanical load on the motor and verify if the fault clears.
Verify parameter P3-01 (Motor rated current) and P3-02 (Motor rated power) match the motor nameplate.
Check for proper drive cooling fan operation and ensure heatsink fins are free of dust or obstructions.
Monitor the drive's internal temperature via parameter P7-10 (Drive temperature).
If the load is appropriate, consider increasing acceleration/deceleration ramps (e.g., P2-01, P2-02) to reduce peak currents.