43

Encoder fault

Vacon · NXS NXP

What does 43 mean?

A problem has been detected with the encoder signals, such as missing channels (A or B), reversed direction, or a missing encoder board. This prevents accurate motor speed and position feedback, leading to unstable or incorrect motor control in closed-loop applications.

Common Causes

  • Encoder feedback cable damage (e.g., broken conductor, short circuit, or shielding fault) leading to signal loss.
  • Improper encoder wiring connections to the drive's encoder option board terminals (e.g., A/A- swapped, 5V/0V shorted).
  • Mechanical damage to the encoder unit itself (e.g., bearing failure, disc misalignment, optical sensor failure).
  • Incorrect encoder configuration parameters (e.g., P4-01 (Encoder type), P4-02 (Pulses per revolution)) not matching the installed encoder.
  • Missing or faulty encoder option board in the drive slot.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Visually inspect the encoder cable for any physical damage from the encoder to the drive.

  2. 2

    Power down the drive and use a multimeter to check for continuity on each conductor of the encoder cable.

  3. 3

    Verify all encoder feedback wires are correctly terminated at the drive's encoder option board (e.g., A, A-, B, B-, Z, Z-, 5V, 0V).

  4. 4

    Check parameter P4-01 (Encoder type) and P4-02 (Pulses per revolution) to ensure they match the installed encoder's specifications.

  5. 5

    Monitor encoder signals using the drive's diagnostic menu (e.g., P4-03 (Encoder speed feedback)) during slow motor rotation.

  6. 6

    If available, swap the encoder option board with a known good one to rule out board failure.

Browse all codes in this manual (54)
Verified technical data. Last updated: April 2026