Vacon · NXS NXP
An option board or power unit has been replaced with a device of a different type or power rating. The drive detects this incompatibility and requires a complete reconfiguration. If parameters are not correctly reset and adjusted, the drive may operate incorrectly, become unstable, or fail to start.
Click steps to track your progress.
Power down the drive completely and verify zero voltage on DC bus terminals.
Identify the recently changed option board or power unit.
Confirm the type and part number of the newly installed component against the application requirements.
Review parameter P7-01 (Slot X Configuration) for the slot where the change occurred.
Adjust parameter P7-01 to "0" (No option board), then power cycle the drive.
Reconfigure the slot by setting P7-01 to the correct value for the newly installed board type and save parameters.