Vacon · NXS NXP
The internal charging switch, which is responsible for pre-charging the DC-link capacitors, remains open when a START command is given. This indicates either an operational malfunction or a defective internal component within the drive. If this fault persists, the drive will be unable to start and operate, signaling a serious internal hardware issue.
Click steps to track your progress.
Measure the incoming AC supply voltage at the drive input terminals (L1, L2, L3) using a true RMS multimeter to ensure it is within the specified operating range (e.g., 380-480VAC).
With power off and safely discharged, inspect the internal charging circuit components (resistors, contactors/relays) for visible damage, arcing, or loose connections.
Attempt a power cycle (turn mains power off for 60 seconds, then on) to reset internal logic and observe if the fault clears.
Measure the DC-link voltage (e.g., terminals DC+ and DC-) immediately after power-up to confirm it attempts to rise during the pre-charge sequence.
If available, use the drive's diagnostic tools (e.g., parameter A5-01 for DC-link voltage) to monitor the pre-charge process.