Communication has been lost between the Master and Follower drives via the SystemBus or CAN communication link. This could be due to incorrect option board parameters or a damaged/disconnected communication cable (optical fibre or CAN). Loss of communication prevents synchronized operation in a master-follower system, leading to operational halts.
Click steps to track your progress.
Inspect SystemBus/CAN communication cable for physical damage, proper seating, and correct pinout between master and follower units.
Measure resistance across the CAN_H and CAN_L terminals at each end of the bus (should be approx. 60 Ohms if correctly terminated).
Verify communication option board (e.g., MCB-103, MCA-101) is securely installed and recognized by the drive (check P8-XX status).
Confirm master drive communication parameters (e.g., P8-10, P8-11 for baud rate) and follower addresses (P8-01) are identical across all connected drives.
Check for proper shielding and grounding of the communication cable to mitigate electromagnetic interference.
Swap communication cable with a known good one to rule out cable fault.