Input Phase Failure
Vacon · NX Liquid-Cooled Drive
What does 10 mean?
An external electronic monitoring relay has detected an undervoltage, incorrect phase sequence, or a phase failure in the input line. The minimum threshold values are 360Vac for 400-500Vac supply and 470Vac for 525-690Vac supply, with a 0.1-second response delay. Possible causes include a missing supply phase, a blown supply fuse, incorrect mains cabling, or a grid interruption. Subcodes S1 (phase supervision diode supply) and S2 (phase supervision active front end) are available.
Common Causes
- Loss of one or more phases on the main AC power input (P0303).
- Internal rectifier failure.
- Loose or disconnected input power wiring.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the settings of the External Monitoring Device (EMD) relay for correct undervoltage thresholds, phase sequence, and response delay.
- 2
Verify the signal wiring from the EMD relay to the control unit.
- 3
Measure the incoming supply voltage at the drive input terminals across all three phases.
- 4
Check all input fuses for continuity and proper rating.
- 5
Inspect the mains cabling for correct phase connections and signs of damage.
- 6
Check the rectifying bridge for proper operation.