EL
ErrorLib
Brands
||
  1. Home
  2. Yaskawa
  3. Drive Fault Codes
  4. EF6
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

EF6

External Fault

Yaskawa · Drive Fault Codes

What does EF6 mean?

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

Common Causes

  • Fault condition from an external safety device (e.g., thermal overload, emergency stop switch, limit switch)
  • Incorrect wiring or loose connection to the S1 terminal, leading to an unintended fault signal
  • Faulty external sensor or switch providing the fault signal to the drive.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect all external devices connected to the S1 terminal for their operational status and reset any tripped devices.

  2. 2

    Verify the integrity of wiring connections to the S1 terminal and check for continuity.

  3. 3

    Measure the voltage signal at the S1 terminal to ensure it is within the expected range (e.g., 24VDC when the fault is clear).

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

CEMEMOBUS/Modbus Communication ErrorCPF02A/D Conversion ErrorCPF03Control Board Connection Error
Source: Yaskawa Drive Fault Codes
Open Manual (Page 2)Search more codes in this manual