Yaskawa · E7 Drive
The rated current set value is set too high, or there's an excessive V/F set value, or a motor iron core saturation coefficient fault, causing the auto-tuning results to be invalid. This is an alarm that indicates incorrect motor or drive parameter settings post-tuning, which could lead to suboptimal performance or protection issues.
Click steps to track your progress.
1. Verify the motor rated current (P2-01) exactly matches the motor nameplate rating. Correct if set too high or too low.
2. Check the V/f pattern parameters (e.g., C2-01 to C2-04) to ensure they are appropriate for the motor type and application, and that the maximum voltage (C2-01) does not exceed the motor's rated voltage.
3. Ensure the correct motor type is selected for auto-tuning (e.g., standard induction motor, permanent magnet motor via P2-08 or H1-01).
4. Perform a factory reset (e.g., A1-03 = 2220) and carefully re-enter all motor and application parameters from scratch before attempting auto-tuning again.
5. If possible, attempt auto-tuning with a different, known-good motor (within drive kVA rating) to isolate if the issue is with the drive or the motor.