Yaskawa · E7 Drive
The motor did not accelerate as specified during the auto-tuning process. This may be due to an acceleration time setting that is too short, torque limits set too low, or the motor being connected to a heavy mechanical load.
Click steps to track your progress.
1. Temporarily increase the acceleration time parameter (e.g., C1-01) by 50% for auto-tuning. Restore to original value after successful tuning.
2. Temporarily set torque limit parameters (L6-01, L6-02) to 150% or disable them during auto-tuning. Restore to production values afterward.
3. Physically disconnect the motor from any mechanical load before initiating auto-tuning, unless the drive explicitly supports tuning with load.
4. Verify all motor nameplate data (rated current, voltage, poles, rated torque) against drive parameters (P2-01 to P2-07).
5. Re-run auto-tuning (e.g., using parameter H3-02 = 1 or 2). If the fault persists, manually rotate the motor shaft to check for mechanical binding.