F6-CEA

Option PCB Communication Error Alarm

Yaskawa · E7 Drive

What does F6-CEA mean?

This alarm occurs when a serial communication option board, attached to the drive at the 2CN connector, detects a communication error, and parameter F6-01 is specifically set to '3: Alarm Only'. In this state, the drive acknowledges the communication issue without energizing the fault output or stopping operation, allowing for continuous monitoring despite communication problems.

Common Causes

  • Option communication board is not fully seated or improperly connected in the drive's 2CN connector slot.
  • Damaged communication cable or loose connections between the option board and the external network (e.g., broken wires, poor crimps).
  • Incorrect communication parameters configured on the option board via drive parameters (e.g., F6-02 for address, F6-03 for baud rate).
  • Faulty or incompatible option board hardware preventing proper communication initialization.
  • Network bus termination resistors are missing or incorrectly configured on the communication bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Power down the drive, firmly re-seat the option communication board into the 2CN connector, and ensure all mounting screws are tightened.

  2. 2

    Visually inspect the communication cable for damage and verify continuity on all conductors using a cable tester.

  3. 3

    Confirm drive parameters F6-02 (Option Board Address), F6-03 (Baud Rate), and F6-04 (Data Format) match the network master's settings.

  4. 4

    Test with a known-good, compatible option board in the 2CN slot to determine if the issue is board-specific.

  5. 5

    Verify proper installation and functionality of network termination resistors at both ends of the communication bus.

  6. 6

    Monitor the communication line with a protocol analyzer or oscilloscope to identify data transmission errors or signal integrity issues.