Yaskawa · E7 Drive
The Overheat (OH) Pre-Alarm indicates that the drive's cooling fin temperature has exceeded the threshold set in parameter L8-02. Depending on the setting of L8-03, this condition can either trigger a fault detection (with the fault contact activating) or function as an alarm only. Ignoring this pre-alarm can lead to a more severe overheat fault (like OH1) and potential damage to the drive if the temperature continues to rise.
Click steps to track your progress.
1. Measure the ambient temperature within the control cabinet using a thermometer and compare it to the drive's specifications.
2. Clear any obstructions blocking the drive's cooling air intake or exhaust vents.
3. Clean dust and debris from the drive's heat sink fins using compressed air (ensure power is off and wear appropriate PPE).
4. Verify the drive cooling fan is operating correctly and producing adequate airflow.
5. Review L8-02 (Overheat Pre-Alarm Level) setting to ensure it is appropriate for the application's operating conditions.