Yaskawa · E7 Drive
The Drive output current exceeded the threshold set in L6-02 for longer than the time set in L6-03, indicating a motor overload condition. This fault protects the motor and mechanical system from damage due to excessive load.
Click steps to track your progress.
1. Measure motor current at U, V, W terminals with a clamp meter and compare to the value set in E2-01 (Motor Rated Current).
2. Inspect the mechanical system (e.g., conveyor, pump, fan) for obstructions, seizing bearings, or misalignments.
3. Verify L6-02 (Overtorque Detection Level) and L6-03 (Overtorque Detection Time) parameters are set appropriately for the application.
4. Check motor winding resistance (U-V, V-W, W-U) with a multimeter for imbalances or open circuits.
5. If continuous overtorque is detected, reduce process load or consider upsizing the motor/drive system.