Yaskawa · E7 Drive
An Operator Programming Error where a run command is selected via serial communication (2CN) but no option board is installed, or it's installed incorrectly. The run command selection parameter B1-02 is set to 3 but the option board is absent. The Drive cannot operate without the correct board and settings.
Click steps to track your progress.
1. Verify the run command source parameter (B1-02) setting. If a serial communication option board is not installed, change B1-02 to a local source (e.g., 'Terminal block' or 'Digital operator').
2. If a serial option board is intended, physically inspect the board for correct installation, ensuring it is fully seated in its designated slot and secured with retaining screws.
3. Check the option board's diagnostic LEDs (if present) for status or error indications. Refer to the option board's manual for LED diagnostic patterns.
4. Power cycle the drive after verifying or adjusting B1-02 and physically installing/re-seating the option board.
5. If using serial communication, ensure the communication parameters (e.g., B3-xx for baud rate, address) are correctly set in the drive and match the external controller.