Yaskawa · E7 Drive
An Operator Programming Error related to incorrect carrier frequency parameter settings, such as C6-05 > 6 and C6-04 > C6-03, or an upper/lower limit error for C6-03 (e.g., set above 5.0kHz). The Drive will not operate until corrected.
Click steps to track your progress.
1. Check the main carrier frequency parameter (C6-03) and ensure it is set strictly within the drive's specified operational range (e.g., typically 2kHz to 15kHz, but often limited to 5kHz for basic models).
2. Review carrier frequency reduction parameters (C6-04, C6-05). Ensure C6-04 (reduction start frequency) is less than C6-03 (main carrier frequency) if reduction is active.
3. If using auto carrier frequency reduction (e.g., C6-05=1 for auto), ensure all related thermal parameters are correctly configured.
4. Reduce the set carrier frequency (C6-03) to a conservative value, such as 3.0kHz, and attempt to run the drive. Gradually increase if needed, while monitoring drive temperature (U1-07).
5. Perform a factory reset (e.g., A1-03 = 2220) and re-enter all parameters, paying close attention to the C6-xx series parameters.