Yaskawa · E7 Drive
This is a warning displayed on the digital operator during a momentary power loss event. It indicates that incoming AC power has been interrupted, but the drive's control power supply is still being maintained. The alarm signifies the drive is in a ride-thru state and will precede a UV1 fault if power is not restored within the configured ride-thru time (L2-02).
Click steps to track your progress.
1. Monitor the incoming AC line voltage at R/L1, S/L2, T/L3 terminals with a power quality analyzer to detect voltage sags.
2. Inspect upstream circuit breakers and fuses for signs of intermittent tripping or loose connections.
3. Confirm all input power wiring connections at the drive are secure and free of corrosion.
4. Verify the drive's ride-through settings (e.g., L2-01) are configured appropriately for the application's power stability.
5. Consider installing a UPS (Uninterruptible Power Supply) for the control circuit or the entire drive if power quality is consistently poor.