Yaskawa · GA500 Maintenance and Troubleshooting
This fault indicates an error with the EEPROM memory data, possibly due to power loss during a parameter write operation from a communication option card or a fault in the EEPROM's peripheral circuit. This can lead to corrupted parameters and incorrect drive functionality.
Click steps to track your progress.
1. Power cycle the drive and observe if the fault clears.
2. Verify stable input power (L1, L2, L3 terminals) during operation, checking for sags or fluctuations.
3. Perform a factory reset (e.g., setting parameter P0-03 to "1" for 10 seconds) to clear corrupted memory.
4. Manually re-enter all motor and application parameters from a known good backup.
5. If using a communication card for parameter writes, try writing parameters directly via the local keypad.
6. Check for loose connections or corrosion on the control board where the EEPROM module or chip is located.