This code indicates a generic hardware problem within the drive's control circuit. This suggests an internal malfunction that could prevent safe and reliable operation and may require internal component inspection or replacement.
Click steps to track your progress.
Record the motor nominal current (P1-01) and any current limit parameters (e.g., P2-03) from the drive's display.
Perform a full power cycle by disconnecting incoming AC power (L1, L2, L3) and waiting for 10 minutes for complete DC bus discharge.
Use a multimeter to verify the integrity of the motor cables (U, V, W) for phase-to-phase shorts or phase-to-ground faults.
Visually inspect the control board, particularly the current sensing circuits and their associated components, for signs of overheating, cracks, or discoloration.
Check for secure connections of internal wiring harnesses that carry current feedback signals from the power stage to the control board.
Attempt a factory parameter reset (e.g., Parameter P9-02) and re-enter essential motor data (P1-XX) and current-related parameters to re-initialize the current sensing logic.