HFB

High Feedback Fault

Yaskawa · iQpump Simplex Pump Drive

What does HFB mean?

The iQpump has detected that the feedback signal level has risen above the programmed threshold (P1-09) and remained above this level for the duration specified in parameter P1-10. This condition triggers a fault, causing the iQpump to coast to a stop for system protection. This fault function is active during running in all operation modes.

Common Causes

  • Feedback signal level rising above the P1-09 (High Feedback Level) threshold.
  • Sustained high feedback level for a period exceeding P1-10 (High Feedback Level Fault Delay Time).
  • Actual high process variable (e.g., system overpressure) in the system.
  • A faulty feedback transducer providing a continuously high signal.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify parameter P1-09 (High Feedback Level) is set to the correct maximum allowable feedback value for the system.

  2. 2

    Verify parameter P1-10 (High Feedback Level Fault Delay Time) is set appropriately to detect sustained issues without nuisance tripping.

  3. 3

    Measure the actual process variable (e.g., pressure) and compare it to the feedback signal reported by the iQpump.

  4. 4

    Check the feedback transducer for proper operation and inspect its wiring and connections for integrity.

Browse all codes in this manual (7)