The iQpump has detected that the feedback signal level has fallen below the programmed threshold set in parameter P1-07. This condition triggers an alarm on the display. The alarm will automatically clear once the feedback level rises above P1-07 plus the Hysteresis Level (P1-13). This alarm function is only active during running in the auto mode.
Click steps to track your progress.
Verify parameter P1-07 (Low Feedback Level) is set to the correct minimum allowable feedback value for the system.
Measure the actual process variable (e.g., pressure) using an independent gauge and compare it to the feedback signal reported by the iQpump.
Inspect the wiring and connections of the feedback transducer for damage or disconnections.
Verify parameter P1-13 (Hysteresis Level) is configured to prevent nuisance alarms due to minor fluctuations.