Yaskawa · iQpump1000
The analog input programmed for PID feedback has risen above 21 mA. This occurs when the PI feedback source is incorrectly installed, not working, or has a wiring issue. The drive's response to this condition is controlled by parameters b5-12 and b5-13.
Click steps to track your progress.
Confirm that the PID feedback source is installed and working properly
Verify the analog input signal for PID feedback is within the expected 3-21 mA range
Check drive parameters b5-12 (Feedback Loss 4 to 20 mA Detection Selection) and b5-13 (Feedback Loss Go To Frequency) for drive response settings