GF

Ground Fault

Yaskawa · iQpump1000

What does GF mean?

A current short to ground exceeding 50% of rated current has been detected on the output side of the drive. This fault is enabled when L8-09 is set to 1. Persistent ground faults can indicate severe motor or cable damage.

Common Causes

  • Motor insulation is damaged.
  • Damaged motor cable creating a short circuit.
  • Excessive leakage current at the drive output.
  • Drive started during a current offset fault or while coasting to a stop.
  • Hardware problem with the control board.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the insulation resistance of the motor.

  2. 2

    Inspect the motor cable for damage, remove any short circuits, and verify resistance between cable and ground terminal.

  3. 3

    Reduce the carrier frequency if excessive leakage current is detected.

  4. 4

    Reduce the amount of stray capacitance.

  5. 5

    Set parameter b3-01 to 1 to enable Speed Search at Start.

  6. 6

    Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.