Yaskawa · iQpump1000
A current short to ground exceeding 50% of rated current has been detected on the output side of the drive. This fault is enabled when L8-09 is set to 1. Persistent ground faults can indicate severe motor or cable damage.
Click steps to track your progress.
Check the insulation resistance of the motor.
Inspect the motor cable for damage, remove any short circuits, and verify resistance between cable and ground terminal.
Reduce the carrier frequency if excessive leakage current is detected.
Reduce the amount of stray capacitance.
Set parameter b3-01 to 1 to enable Speed Search at Start.
Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.