Yaskawa · iQpump1000
The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10. This fault is effective only when Q5-11 (Low Suction Pressure Behavior Select) is set to 2 (fault).
Click steps to track your progress.
Increase the system pressure.
Set the Low Suction fault characteristics using parameters Q5-09, Q5-10, and Q5-18.
Control drive response to this condition using Q5-11 (Low Suction Pressure Behavior Select).
Control auto-restart of this fault using Q5-11 (Low Suction Pressure Behavior Select) and Q5-15 (Suction Pressure Auto-restart Time).