Yaskawa · J1000
The MECHATROLINK communication watchdog timer has timed out because the drive did not receive expected data from the PLC within the specified timeframe. This indicates a loss of communication or a significant delay in data exchange over the MECHATROLINK network, which can lead to a complete loss of control over the drive.
Click steps to track your progress.
Verify the physical integrity and secure connection of the MECHATROLINK communication cable at both the drive and the PLC.
Check the status LEDs on the drive's MECHATROLINK port and the PLC's communication module for specific error codes or communication activity indicators.
Confirm that the drive's MECHATROLINK station address (e.g., F8-01) is unique and correctly set according to the network topology.
Review the PLC program and MECHATROLINK configuration for the master device, ensuring it is actively scanning and sending data to the drive's assigned address.
Measure the network cable continuity and shield integrity using a cable tester to rule out damaged conductors or improper grounding.
Increase the MECHATROLINK watchdog timer setting (e.g., parameter F8-04) temporarily to a higher value (e.g., 500ms) to see if the fault is timing-related.