A command to switch motors was entered while the drive was still in run mode. This operation is typically disallowed to prevent incorrect motor control, unexpected behavior, or potential damage to the motors or drive components.
Click steps to track your progress.
Ensure the drive is in a fully stopped state (output frequency 0Hz, Run command inactive) before any attempt to change motor selections.
Review the master controller (e.g., PLC, HMI) logic to confirm that motor selection commands are only issued when the drive's Run command is inactive.
Verify the integrity of input terminals assigned to motor selection (e.g., H1-03) by measuring their state with a multimeter to ensure they are open (inactive) unless intentionally switched.
Check relevant parameters for multi-motor operation (e.g., A1-03, A1-04, A1-05 for motor data sets) to confirm proper configuration for sequential operation.
Monitor the status of the specific multi-function input bit (e.g., U1-01) in the drive's monitor menu to confirm it is not inadvertently toggled during operation.