Yaskawa · J1000
The soft-charge bypass circuit has failed, typically due to a damaged relay or contactor within this circuit. This failure can prevent proper charging of the DC bus, leading to the drive being unable to start or operate correctly.
Click steps to track your progress.
1. With power off and discharged, use an ohmmeter to check the resistance of the pre-charge resistor; it should be finite and not an open circuit.
2. Visually inspect the soft-charge bypass relay/contactor for signs of arcing, physical damage, or improper operation.
3. Check the control voltage output from the drive's internal circuit that energizes the soft-charge relay coil during the power-up sequence.
4. Verify the DC bus capacitors for any physical swelling, leakage, or signs of overheating, which could indicate a failure.
5. Confirm that the drive's internal diagnostics correctly detect the state of the soft-charge circuit components (if accessible).
6. If external components are functional, the internal soft-charge control circuit on the drive's power board may be faulty; replace the drive.