CE

MEMOBUS Communication Error

Yaskawa · VS-616G5 Variable Speed Drive

What does CE mean?

This fault occurs when communication via MODBUS (MEMOBUS) is interrupted for longer than 2 seconds after initial communication has been established. This indicates a loss of data exchange with the control system or HMI, which can lead to uncontrolled operation, system downtime, or failure to receive critical commands.

Common Causes

  • Damaged or improperly connected RS-485 communication cable (e.g., A/B lines reversed or open circuit).
  • Incorrect MODBUS parameters (e.g., P5-01 Baud rate, P5-02 Data bits/Parity, P5-03 Station address) configured in the inverter or master device.
  • Missing or incorrect termination resistor on the MODBUS network (e.g., 120 ohm resistor across A and B lines).
  • Excessive electrical noise or ground loops on the communication bus interfering with data integrity.
  • Overloaded MODBUS network with too many devices or excessive cable length beyond specifications.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect RS-485 cable connections at inverter terminals S+, S- and the master controller, ensuring correct polarity (A to A, B to B).

  2. 2

    Verify MODBUS parameters P5-01 (Baud rate), P5-02 (Data bits/Parity), and P5-03 (Station address) match between inverter and master.

  3. 3

    Measure the voltage across RS-485 terminals S+ and S- (typically differential 0.2V to 5V during communication) using an oscilloscope.

  4. 4

    Confirm the presence and correct placement of 120-ohm termination resistors at both ends of the RS-485 bus.

  5. 5

    Test communication with a single known good MODBUS master directly connected to the inverter to isolate network issues.

Browse all codes in this manual (34)
Verified technical data. Last updated: April 2026

Related Faults

BUSSI-B Communication ErrorCPF5CPU A/D Converter FaultDEVExcessive Speed Deviation
Source: Yaskawa VS-616G5 Variable Speed Drive
View Official PDFSearch more codes in this manual