Yaskawa · VS-616G5 Variable Speed Drive
This fault indicates an internal malfunction within the inverter's CPU, specifically related to its Analog-to-Digital (A/D) converter. It suggests a problem with the inverter's ability to accurately read analog signals, which is critical for its control functions. Input phase loss detection is disabled under this condition.
Click steps to track your progress.
1. Power cycle the inverter (disconnect main power for 60 seconds) to attempt a software and hardware reset of the CPU.
2. Isolate the inverter from external analog input signals (e.g., disconnect wires from AI1, AI2 terminals) and re-power to determine if an external signal is causing the fault.
3. Measure the incoming analog input signals (voltage or current) directly at the source to ensure they are within the expected range (e.g., 0-10VDC, 4-20mA) and free of excessive noise.
4. Check the inverter's cooling fan operation and heatsink for dust buildup to ensure proper heat dissipation from internal components.
5. If available, attempt to reload the inverter's firmware using the manufacturer's specified procedure and software tool.